########## Modbus TCP ########## Most used properties are in italics. alias Alias that is used instead of full point path and name in quickSources and quickTargets for example *enabled* True = port is enabled, false = port is disabled and no database points will read from or write to it busType Port type for Actiweb internal workings byteTimeout(microseconds) Timeout for individual bytes in modbus packages *delayBetweenFrames (microseconds)* Delay between modbus frames. Some slave devices need more time between frames. ipAddress what IP-address the server will use to bound itself to. Usually same value is used as the controllers IP-address. If left blank, will default to `127.0.0.1` mode Select if port is being used as master of slave *responseTimeout (microseconds)* Time spent waiting for a response from modbusdevice Read frame will give timeout-error if response time exceeds this value taskSleepTime (milliseconds) How long task will wait after full round of requests have been done. *tcpPort* What tcp port will be used to listen Modbus traffic. .. important:: As of now, in ``slave`` mode the default modbusport ``502`` *cannot* be used for security reasons. Only ports above 1024 are permitted. writeMode: Switch for the logic how writable points will be written to the slave device always: Points will be written every round changes and cyclic: Points will be periodicly written, but also always when the value changes changes only: Points will be written to the slave only when they change read only: Writing will be disabled (used mainly for debugging)